Wire gauge chart (AWG)

Find any AWG size’s diameter, cross-section and resistance, with copper and aluminium side by side. Need the amp rating rather than the size? Use the ampacity chart, or see the conduit fill tool for conduit sizing.

INPUT
RESULT
Load
20 A at 120 V
One-way run
100 ft
Ampacity column
75 °C copper
Smallest size by ampacity
12 AWG
Smallest size by voltage drop (3 %)
8 AWG
Use at least
8 AWG
Voltage drop at that size
2.51 V · 2.09 %
Usable ampacity of that size
50 A

Voltage drop = 2 × length × current × ohm per 1000 ft ÷ 1000, copper at 20 °C. Ampacity from NFPA 70 Table 310.16 for copper at 30 °C ambient with no more than three current-carrying conductors, limited to 15 A, 20 A and 30 A for 14, 12 and 10 AWG by NEC 240.4(D); sizes 18 and 16 have no value in that table.

AWG sizes with diameter and resistance

Measure the bare conductor with calipers and match the diameter in the chart; 12 AWG solid is about 0.081 inch, 14 AWG about 0.064. On cable, the gauge is usually printed on the jacket. Stranded wire is slightly larger than solid of the same gauge.

Electrical gauge wire chart: AWG 14 to 4/0 with diameter, resistance and ampacity
Copper wire sizes with diameter and ampacity columns.

Resistance turns the size into a voltage drop. For a two-wire circuit, drop = 2 × length × current × ohm per 1000 ft ÷ 1000. At 20 A over 100 ft, 12 AWG (1.588 ohm per 1000 ft) drops 6.35 V, while 8 AWG (0.628 ohm per 1000 ft) drops 2.51 V, which is 2.09 % of 120 V.

Full AWG reference table

The table lists every AWG size from 4/0 down to 30 with diameter, area and DC resistance for copper and aluminium. Values follow the AWG formula (ASTM B258) at 20 °C, with copper at 1.724 µΩ·cm and 1350 aluminium at 2.82 µΩ·cm, so you can compute voltage drop or compare with metric cable. NEC Chapter 9 Table 8 prints DC resistance at 75 °C, which is higher.

AWG Diameter (in) Diameter (mm) Area (kcmil) Area (mm²) Copper (ohm per 1000 ft) Aluminium (ohm per 1000 ft)
4/0 0.4600 11.684 211.6 107.22 0.049 0.080
3/0 0.4096 10.405 167.8 85.03 0.062 0.101
2/0 0.3648 9.266 133.1 67.43 0.078 0.127
1/0 0.3249 8.251 105.5 53.48 0.098 0.161
1 0.2893 7.348 83.7 42.41 0.124 0.203
2 0.2576 6.544 66.4 33.63 0.156 0.256
3 0.2294 5.827 52.6 26.67 0.197 0.322
4 0.2043 5.189 41.7 21.15 0.248 0.406
5 0.1819 4.621 33.1 16.77 0.313 0.512
6 0.1620 4.115 26.3 13.30 0.395 0.646
7 0.1443 3.665 20.8 10.55 0.498 0.815
8 0.1285 3.264 16.5 8.37 0.628 1.028
9 0.1144 2.906 13.1 6.63 0.792 1.296
10 0.1019 2.588 10.4 5.26 0.999 1.634
11 0.0907 2.305 8.2 4.17 1.260 2.060
12 0.0808 2.053 6.5 3.31 1.588 2.598
13 0.0720 1.828 5.2 2.62 2.003 3.276
14 0.0641 1.628 4.1 2.08 2.525 4.131
15 0.0571 1.450 3.3 1.65 3.184 5.209
16 0.0508 1.291 2.6 1.31 4.015 6.568
17 0.0453 1.150 2.0 1.04 5.063 8.282
18 0.0403 1.024 1.6 0.82 6.385 10.444
19 0.0359 0.912 1.3 0.65 8.051 13.170
20 0.0320 0.812 1.0 0.52 10.152 16.607
21 0.0285 0.723 0.8 0.41 12.802 20.940
22 0.0253 0.644 0.6 0.33 16.143 26.405
23 0.0226 0.573 0.5 0.26 20.356 33.297
24 0.0201 0.511 0.4 0.20 25.668 41.986
25 0.0179 0.455 0.3 0.16 32.367 52.944
26 0.0159 0.405 0.3 0.13 40.814 66.761
27 0.0142 0.361 0.2 0.10 51.466 84.184
28 0.0126 0.321 0.2 0.08 64.897 106.154
29 0.0113 0.286 0.1 0.06 81.834 133.858
30 0.0100 0.255 0.1 0.05 103.190 168.791
The wire size finder showing 8 AWG for a 20 A load at 120 V over a 100 ft run
Screenshot: the wire size finder on this page with a 20 A, 120 V, 100 ft example.

Which is thicker, 12 or 14 gauge

In AWG a smaller number means a thicker wire, so 12 is thicker than 14, 16 or 20. Every drop of three gauge numbers roughly doubles the cross-section. That is why 12 AWG can carry more current than 14 AWG on the same circuit.

In the table, 14 AWG has 2.08 mm² and 12 AWG has 3.31 mm², about 1.6 times as much copper. For what each size may carry, see the ampacity chart. The page does not replace a licensed electrician or your local code; local amendments and inspectors have the final say.

More about the site is on the about conduitwise page.