Skip to content

Ampacity Wire Gauge Chart

Ampacity of copper wire from 14 AWG to 4/0 at 60, 75 and 90 degrees C

An ampacity wire gauge chart lists how many amps each wire size can carry. Pick copper or aluminum, the insulation rating, the ambient temperature and the number of conductors, and the tool gives the smallest size for your load. Table values come from NFPA 70 Table 310.16.

INPUT
RESULT
Smallest size
8 AWG copper
Table ampacity
55 A (90 °C)
Temperature factor
0.91
Adjustment factor
0.8
Adjusted ampacity
40.04 A

Adjusted = 55 × 0.91 × 0.8 = 40.04 A, never more than the 50 A allowed by the 75 °C terminals. Check local code and hire a licensed electrician.

SizeTable (A)Adjusted (A)Terminal cap (A)Usable (A)

Worked example: 35 A load, 40 °C, six conductors

THHN copper wire (90 °C) runs in one conduit with six current-carrying conductors in a 40 °C space, ending on 75 °C terminals, and the load is 35 A. For 8 AWG the 90 °C table value is 55 A. The 40 °C ambient factor for the 90 °C column is 0.91 and six conductors call for 80 percent, so 55 × 0.91 × 0.8 = 40.04 A. The 75 °C terminals allow 50 A, so 40.04 A stands, and it is at least 35 A. 10 AWG gives 40 × 0.91 × 0.8 = 29.12 A, which is too small. The answer is 8 AWG.

Derating example: 8 AWG copper at 55 A times 0.91 times 0.8 gives 40.04 A for a 35 A load

Ampacity chart: copper

Size 60 °C (A) 75 °C (A) 90 °C (A)
14 AWG 15 20 25
12 AWG 20 25 30
10 AWG 30 35 40
8 AWG 40 50 55
6 AWG 55 65 75
4 AWG 70 85 95
3 AWG 85 100 115
2 AWG 95 115 130
1 AWG 110 130 145
1/0 AWG 125 150 170
2/0 AWG 145 175 195
3/0 AWG 165 200 225
4/0 AWG 195 230 260
250 kcmil 215 255 290
300 kcmil 240 285 320
350 kcmil 260 310 350
400 kcmil 280 335 380
500 kcmil 320 380 430

Ampacity chart: aluminum and copper-clad aluminum

Size 60 °C (A) 75 °C (A) 90 °C (A)
12 AWG 15 20 25
10 AWG 25 30 35
8 AWG 30 40 45
6 AWG 40 50 55
4 AWG 55 65 75
3 AWG 65 75 85
2 AWG 75 90 100
1 AWG 85 100 115
1/0 AWG 100 120 135
2/0 AWG 115 135 150
3/0 AWG 130 155 175
4/0 AWG 150 180 205
250 kcmil 170 205 230
300 kcmil 195 230 260
350 kcmil 210 250 280
400 kcmil 225 270 305
500 kcmil 260 310 350
Copper compared with aluminum ampacity at 75 degrees C by wire size

Ambient temperature correction

The table above assumes a 30 °C ambient. At other temperatures multiply the ampacity by these factors. A dash means that insulation rating is not allowed at that temperature.

Ambient 60 °C 75 °C 90 °C
10 °C or less 1.29 1.2 1.15
11–15 °C 1.22 1.15 1.12
16–20 °C 1.15 1.11 1.08
21–25 °C 1.08 1.05 1.04
26–30 °C 1.00 1.00 1.00
31–35 °C 0.91 0.94 0.96
36–40 °C 0.82 0.88 0.91
41–45 °C 0.71 0.82 0.87
46–50 °C 0.58 0.75 0.82
51–55 °C 0.41 0.67 0.76
56–60 °C — 0.58 0.71
61–65 °C — 0.47 0.65
66–70 °C — 0.33 0.58

Adjustment for more than three conductors

When more than three current-carrying conductors share a raceway or cable, multiply by the percentage below.

Current-carrying conductors Multiply by
1–3 100 %
4–6 80 %
7–9 70 %
10–20 50 %
21–30 45 %
31–40 40 %
41 and over 35 %

About these numbers

The values follow NFPA 70, the National Electrical Code, Table 310.16 (formerly 310.15(B)(16)), Table 310.15(B)(1) and Table 310.15(C)(1), as numbered in the 2023 edition. We have not checked them against the licensed text of every edition on this site, so confirm with your own copy of the code and your local amendments. Small copper conductors are also limited by overcurrent protection rules: 14 AWG to 15 A, 12 AWG to 20 A and 10 AWG to 30 A. Follow local code and hire a licensed electrician; this page is not a substitute for a design.

Frequently asked questions

What is ampacity?

Ampacity is the largest current, in amps, that a wire can carry continuously without its insulation getting hotter than its rating. It depends on the wire size, the metal, the insulation temperature rating and the conditions around the wire.

What is the ampacity of 12 AWG copper wire?

In the NEC table, 12 AWG copper is 20 A at 60 °C, 25 A at 75 °C and 30 A at 90 °C. The code also limits overcurrent protection for 12 AWG copper to 20 A, so the usable figure for ordinary circuits is 20 A.

Why is aluminum rated lower than copper?

Aluminum conducts less current than copper of the same size, so the table lists lower ampacities, for example 40 A for 8 AWG aluminum against 50 A for copper at 75 °C. Aluminum also needs terminals listed for it.

Do I use the 90 °C column to size the wire?

You may start from the 90 °C column to apply temperature and conductor-count corrections, but the final ampacity may not be higher than the value for the 60 °C or 75 °C terminals the wire connects to. The tool above applies that cap.

Wiring an audio amplifier instead? See the amplifier wire gauge chart, and for a size by voltage drop use the electrical gauge wire chart.

INSPECTION TAG

Did this tool pass inspection?

Mark it as passed, or send it back for rework with a note.

TOOLBOX INDEX

Shop and auto