Wire Cable Gauge Chart
Read a cable label like 14/2 or 12/3 and see what wire is inside. Pick a size from 20 AWG to 4/0, or type the bare wire width you measured, and the tool names the nearest gauge and decodes the label. Need diameters and resistance for every AWG size? The full AWG reference has them.
- Size
- 12 AWG
- Diameter
- 0.0808 in (2.053 mm)
- Area
- 3.31 mm²
- Circular mils
- 6,530
- Resistance, copper
- 1.588 ohm per 1000 ft
- Ampacity 60 / 75 / 90 °C
- 20 / 25 / 30 A
- Cable label
- 12/3 = 3 insulated wires + bare ground
Overcurrent protection for 12 AWG copper is limited to 20 A. Check local code and hire a licensed electrician.
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Ohm per 1000 ft |
|---|
What 14/2, 12/3 and 10/2 mean
On building cable, the first number is the wire gauge and the second is the number of insulated conductors, not counting the bare ground. So 14/2 has two 14 AWG wires plus a ground, and 12/3 has three 12 AWG wires plus a ground, used for three-way switches or split circuits.
Worked example. A caliper reads 1.63 mm on a stripped wire. The AWG formula gives 14 AWG as 0.127 × 92^((36 − 14) ÷ 39) = 1.628 mm, and 12 AWG is 2.053 mm, so 1.63 mm is 14 AWG. Its area is π × 1.628² ÷ 4 = 2.08 mm², and copper at 20 °C (17.241 nΩ·m) gives 8.29 mΩ per meter, or 2.525 ohm per 1000 ft.

Cable labels and the circuits they serve
The lookup lists common NM-B cable labels with the conductor count, the breaker they usually pair with under the NEC, and typical uses: 14/2 on 15 A lighting, 12/2 on 20 A outlets, 10/2 on 30 A water heaters. Pick a label to see its row.
| Cable label | Gauge | Insulated wires | Usual breaker | Typical use |
|---|---|---|---|---|
| 14/2 | 14 AWG | 2 + ground | 15 A | Lighting circuits |
| 14/3 | 14 AWG | 3 + ground | 15 A | Three-way switch loops |
| 12/2 | 12 AWG | 2 + ground | 20 A | Outlet circuits in kitchens and garages |
| 12/3 | 12 AWG | 3 + ground | 20 A | Three-way switches or split circuits |
| 10/2 | 10 AWG | 2 + ground | 30 A | Water heaters |
| 10/3 | 10 AWG | 3 + ground | 30 A | Dryer circuits |
| 8/2 | 8 AWG | 2 + ground | 40 A | Large 240 V appliances |
| 8/3 | 8 AWG | 3 + ground | 40 A | Ranges and ovens |
| 6/2 | 6 AWG | 2 + ground | 50 A | Sub-feeds and EV chargers |
| 6/3 | 6 AWG | 3 + ground | 50 A | Ranges with 120/240 V |
Source: NFPA 70 (NEC) 240.4(D) and Table 310.16, copper, 60 °C column. The ground wire is not counted in the label.

When the label is not the whole story
The label tells you the gauge, but long runs, hot spaces and aluminium wire all change what the cable can safely carry. Check the ampacity chart for the full limits, and follow your local code for the places where NM cable is allowed. See amps per wire size.
Breaker pairings are the common NEC defaults for copper NM-B; local code and an electrician decide the final installation.
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Circular mils | Ohm per 1000 ft | 60 °C (A) | 75 °C (A) | 90 °C (A) |
|---|---|---|---|---|---|---|---|---|
| 20 | 0.0320 | 0.812 | 0.52 | 1,022 | 10.15 | — | — | — |
| 18 | 0.0403 | 1.024 | 0.82 | 1,624 | 6.385 | — | — | — |
| 16 | 0.0508 | 1.291 | 1.31 | 2,583 | 4.015 | — | — | — |
| 14 | 0.0641 | 1.628 | 2.08 | 4,107 | 2.525 | 15 | 20 | 25 |
| 12 | 0.0808 | 2.053 | 3.31 | 6,530 | 1.588 | 20 | 25 | 30 |
| 10 | 0.1019 | 2.588 | 5.26 | 10,383 | 0.999 | 30 | 35 | 40 |
| 8 | 0.1285 | 3.264 | 8.37 | 16,510 | 0.628 | 40 | 50 | 55 |
| 6 | 0.1620 | 4.115 | 13.30 | 26,251 | 0.395 | 55 | 65 | 75 |
| 4 | 0.2043 | 5.189 | 21.15 | 41,741 | 0.248 | 70 | 85 | 95 |
| 3 | 0.2294 | 5.827 | 26.67 | 52,635 | 0.197 | 85 | 100 | 115 |
| 2 | 0.2576 | 6.544 | 33.63 | 66,371 | 0.156 | 95 | 115 | 130 |
| 1 | 0.2893 | 7.348 | 42.41 | 83,693 | 0.124 | 110 | 130 | 145 |
| 1/0 | 0.3249 | 8.251 | 53.48 | 105,535 | 0.098 | 125 | 150 | 170 |
| 2/0 | 0.3648 | 9.266 | 67.43 | 133,077 | 0.078 | 145 | 175 | 195 |
| 3/0 | 0.4096 | 10.405 | 85.03 | 167,806 | 0.062 | 165 | 200 | 225 |
| 4/0 | 0.4600 | 11.684 | 107.22 | 211,600 | 0.049 | 195 | 230 | 260 |
Diameters come from the AWG definition in ASTM B258: 36 AWG is 0.005 in and 0000 is 0.46 in, with 92 steps between them, so d = 0.127 mm × 92^((36 − n) ÷ 39). Resistance uses annealed copper at 20 °C. Ampacity is copper, from NFPA 70 (NEC) Table 310.16 as numbered in the 2023 edition. This page is a reference, not a design.

By Conduitwise · Updated: November 18, 2026 · Figures come from named public standards or from the formulas shown on this page.