Wire Cable Gauge Chart

Read a cable label like 14/2 or 12/3 and see what wire is inside. Pick a size from 20 AWG to 4/0, or type the bare wire width you measured, and the tool names the nearest gauge and decodes the label. Need diameters and resistance for every AWG size? The full AWG reference has them.

INPUT
RESULT
Size
12 AWG
Diameter
0.0808 in (2.053 mm)
Area
3.31 mm²
Circular mils
6,530
Resistance, copper
1.588 ohm per 1000 ft
Ampacity 60 / 75 / 90 °C
20 / 25 / 30 A
Cable label
12/3 = 3 insulated wires + bare ground

Overcurrent protection for 12 AWG copper is limited to 20 A. Check local code and hire a licensed electrician.

AWGDiameter (in)Diameter (mm)Area (mm²)Ohm per 1000 ft

What 14/2, 12/3 and 10/2 mean

On building cable, the first number is the wire gauge and the second is the number of insulated conductors, not counting the bare ground. So 14/2 has two 14 AWG wires plus a ground, and 12/3 has three 12 AWG wires plus a ground, used for three-way switches or split circuits.

Worked example. A caliper reads 1.63 mm on a stripped wire. The AWG formula gives 14 AWG as 0.127 × 92^((36 − 14) ÷ 39) = 1.628 mm, and 12 AWG is 2.053 mm, so 1.63 mm is 14 AWG. Its area is π × 1.628² ÷ 4 = 2.08 mm², and copper at 20 °C (17.241 nΩ·m) gives 8.29 mΩ per meter, or 2.525 ohm per 1000 ft.

A 1.63 mm bare copper wire is 14 AWG, 2.08 mm² and 2.525 ohm per 1000 ft
Illustration: a 1.63 mm bare wire is 14 AWG

Cable labels and the circuits they serve

The lookup lists common NM-B cable labels with the conductor count, the breaker they usually pair with under the NEC, and typical uses: 14/2 on 15 A lighting, 12/2 on 20 A outlets, 10/2 on 30 A water heaters. Pick a label to see its row.

Cable label Gauge Insulated wires Usual breaker Typical use
14/2 14 AWG 2 + ground 15 A Lighting circuits
14/3 14 AWG 3 + ground 15 A Three-way switch loops
12/2 12 AWG 2 + ground 20 A Outlet circuits in kitchens and garages
12/3 12 AWG 3 + ground 20 A Three-way switches or split circuits
10/2 10 AWG 2 + ground 30 A Water heaters
10/3 10 AWG 3 + ground 30 A Dryer circuits
8/2 8 AWG 2 + ground 40 A Large 240 V appliances
8/3 8 AWG 3 + ground 40 A Ranges and ovens
6/2 6 AWG 2 + ground 50 A Sub-feeds and EV chargers
6/3 6 AWG 3 + ground 50 A Ranges with 120/240 V

Source: NFPA 70 (NEC) 240.4(D) and Table 310.16, copper, 60 °C column. The ground wire is not counted in the label.

The cable label lookup with 12/2 selected
Screenshot: the lookup on this page with a worked example

When the label is not the whole story

The label tells you the gauge, but long runs, hot spaces and aluminium wire all change what the cable can safely carry. Check the ampacity chart for the full limits, and follow your local code for the places where NM cable is allowed. See amps per wire size.

Breaker pairings are the common NEC defaults for copper NM-B; local code and an electrician decide the final installation.

AWG Diameter (in) Diameter (mm) Area (mm²) Circular mils Ohm per 1000 ft 60 °C (A) 75 °C (A) 90 °C (A)
20 0.0320 0.812 0.52 1,022 10.15 — — —
18 0.0403 1.024 0.82 1,624 6.385 — — —
16 0.0508 1.291 1.31 2,583 4.015 — — —
14 0.0641 1.628 2.08 4,107 2.525 15 20 25
12 0.0808 2.053 3.31 6,530 1.588 20 25 30
10 0.1019 2.588 5.26 10,383 0.999 30 35 40
8 0.1285 3.264 8.37 16,510 0.628 40 50 55
6 0.1620 4.115 13.30 26,251 0.395 55 65 75
4 0.2043 5.189 21.15 41,741 0.248 70 85 95
3 0.2294 5.827 26.67 52,635 0.197 85 100 115
2 0.2576 6.544 33.63 66,371 0.156 95 115 130
1 0.2893 7.348 42.41 83,693 0.124 110 130 145
1/0 0.3249 8.251 53.48 105,535 0.098 125 150 170
2/0 0.3648 9.266 67.43 133,077 0.078 145 175 195
3/0 0.4096 10.405 85.03 167,806 0.062 165 200 225
4/0 0.4600 11.684 107.22 211,600 0.049 195 230 260

Diameters come from the AWG definition in ASTM B258: 36 AWG is 0.005 in and 0000 is 0.46 in, with 92 steps between them, so d = 0.127 mm × 92^((36 − n) ÷ 39). Resistance uses annealed copper at 20 °C. Ampacity is copper, from NFPA 70 (NEC) Table 310.16 as numbered in the 2023 edition. This page is a reference, not a design.

Cable label 12/3 means 12 AWG with 3 insulated wires plus a bare ground
Illustration: what the label 12/3 counts

By Conduitwise · Updated: November 18, 2026 · Figures come from named public standards or from the formulas shown on this page.